ACE-540A
24V DC Output Industrial Power Supply

Features
Input
: Voltage : 85 ~ 264V AC
Output :
-2A@24V DC, 50ºC with 20CFM air cooling
-1.7A@24V DC, 50ºC with free air cooling
Load Regulation : Less than +/-1% by changing the output
Efficiency : Higher than 70%
Hold-up Time : 20ms (typical)@115V AC
Protection : Over voltage protection.
The trip point is around 26.2V ~ 31V output
Operating Temperature : -20ºC ~ 70ºC
(Will derate the output to 70% when operating at 70ºC)
Storage Temperature : -40ºC ~ 85ºC
Altitude : 0 ~ 10,000ft
MTBF : 396,220 Hours.
Safety : UL 1950, CSA 22.2 No. 234, VDE EN 60950
EMI : FCC docket 20780 curve "B", EN55022
EMS Standard :
- EN-50082-1
- IEC 801-2 8KV (Air Discharge) criteria B
- IEC 801-3, 3V/M criteria B
- IEC 801-4, 2KV criteria B
- IEC 801-5, 2KV criteria B
|