The ET-7060, a web-based Ethernet I/O module, features a built-in web server, which allows configuration, I/O monitoring and I/O control by simply using a regular web browser. Besides, with the web HMI function, no more programming or HTML skills are needed; creating dynamic and attractive web pages for I/O monitoring and I/O control would be fun to engineers ever after. The ET-7060 offers easily and safely access for users from anytime and anywhere! In addition, the ET-7060 also supports Modbus/TCP protocol that makes perfect integration for ET-7060 to SCADA software.
The ET-7060 provides 6 power relay (form A) output and 6 isolated wet contact (sink, source type) digital input channels. Each power relay supports contact rating as 5A@250Vac or 5A@30Vdc and each digital input channel supports counter input (32 bits and 500Hz max.)
| CPU | |||
| CPU | 80186 CPU (80MHz) | ||
| SRAM | 512K Bytes | ||
| Flash Memory | 512K Bytes | ||
| EEPROM | 16K Bytes | ||
| Dual Watchdog | Yes | ||
| Communication | |||
| Ethernet Port | 10 / 100 Base TX (With Link, Activity LED Indicator) Automatic MDI/MDI-X Crossover |
||
| Relay Output | |||
| Output Channels | 6 | ||
| Output Type | Power Relay, Form A (SPST N.O.) | ||
| Operating Voltage Range |
250 Vac / 30Vdc |
||
| Max. Load Current | 5.0A/channel at 25 °C | ||
| Operate Time | 6ms | ||
| Release Time | 3ms | ||
| Electrical Life ( Resistive load ) | VDE: | 5A 250Vac 30,000 ops (10 ops/minute) at 75°C. | |
| 5A 30Vdc 70,000 ops (10 ops/minute) at 75°C. | |||
| UL: | 5A 250Vac/30Vdc 6,000 ops. | ||
| 3A 250Vac/30Vdc 100,000 ops. | |||
| Mechanical Life | 20,000,000 ops. at no load (300 ops./minute). | ||
| Digital Input | |||
| Input Channels | 6 | ||
| Input Type | Wet Contact (Sink, Source) | ||
| On Voltage Level | +10Vdc to 50Vdc | ||
| Off Voltage Level | +4Vdc max. | ||
| Input Impedance | 10K Ohms | ||
| Counters | Max. Count: 4,294,967,285 (32 bits) | ||
| Max. Input Frequency : 500Hz | |||
| Min. Pulse Width: 1 ms | |||
| Overvoltage Protection | +70Vdc | ||
| 2 Way Isolation | |||
| Ethernet | 1500 Vrms | ||
| I/O | DI | 3750 Vrms | |
| Relay Output | 3000 Vrms | ||
| Mounting | |||
| Din Rail Mount | Yes | ||
| Wall Mount | Yes | ||
| Power Requirements | |||
| Protection | Power reverse polarity protection | ||
| Required Supply Voltage | +10Vdc to 30Vdc (non-regulated) | ||
| LED Indicator | Yes | ||
| Power Consumption | 0.12A/24Vdc Max. | ||
| Environment | |||
| Operating Temperature | -25 ~ +75 °C | ||
| Storage Temperature | -30 ~ +80 °C | ||
| Relative Humidity | 5 to 90% RH, non-condensing | ||
| Certification | CE, FCC | ||
| Dimensions | |||