The ET-7017-10, a web-based Ethernet I/O module, features a built-in web server, which allows configuration, I/O monitoring and I/O control by simply using a regular web browser. Besides, with the web HMI function, no more programming or HTML skills are needed; creating dynamic and attractive web pages for I/O monitoring and I/O control would be fun to engineers ever after. The ET-7017-10 offers easy and safe access for users from anytime and anywhere! In addition, ET-7017-10 also supports Modbus/TCP protocol that makes seamless integration to SCADA software.
The ET-7017-10 is a 16-bit, 10-channel differential or 20-channel single-ended analog inputs module that provides programmable input range on all analog channels(+/-150mV, +/-500mV, +/-1V, +/-5V, +/-10V, +/-20mA, 0~20mA and 4~20mA). Each analog channel is allowed to configure an individual range and has 240Vrms high over voltage protection. Jumper selectable for voltage or current input.
| CPU | |
| CPU | 80186 CPU (80MHz) |
| SRAM | 512K Bytes |
| Flash Memory | 512K Bytes |
| EEPROM | 16K Bytes |
| Dual Watchdog | Yes |
| Communication | |
| Ethernet Port | 10 / 100 Base-TX (With Link, Activity LED Indicator) Automatic MDI/MDI-X Crossover |
| Analog Input | |
| Input Channels | 10 differential or 20 single-ended (Note1), software selectable |
| Input Type | +/-150mV, +/-500mV, +/-1V, +/-5V, +/-10V +/-20mA ,0~20mA, 4~20mA (jumper selectable) |
| Resolution | 16-bit (Normal Mode) / 12-bit (Fast Mode) |
| Sampling Rate | 10 samples/ second (Normal Mode) / 50 samples/ second (Fast Mode) total |
| Accuracy | +/-0.1% (Normal Mode) / +/-0.5% (Fast Mode) or better |
| BandWidth | 15.7Hz (Normal Mode) / 78.7Hz (Fast Mode) |
| Zero drift | +/-20uV/°C |
| Span drift | +/-25ppm/°C |
| Input Impedance | Voltage: 2M Ohms(Differential), 1M Ohms(Single-ended) /Current: 125 Ohms |
| Common Mode Rejection | 86dB min. |
| Normal Mode Rejection | 100dB |
| Individual Channel Configuration | Yes |
| Over Voltage Protection | Differential: 240 Vrms, Single-ended: 150Vrms |
| ESD Protection | 4KV Contact for each terminal, and 8KV Air for random point |
| EFT Protection | 4KV for Power |
| 2 Way Isolation | |
| Ethernet | 1500 V DC |
| AI and DO | 2500 V DC |
| Mounting | |
| Din Rail Mount | Yes |
| Wall Mount | Yes |
| LED Display | |
| L1 LED as Run indicator, L2 LED as Link/Act indicator, L3 LED as 10/100M indicator | |
| Power Requirements | |
| Protection | Power reverse polarity protection |
| Required Supply Voltage | +10Vdc to 30Vdc (non-regulated) |
| Power consumption | 0.11A/24V DC |
| Environment | |
| Operating Temperature | -25°C to +75°C |
| Storage Temperature | -30°C to +80°C |
| Relative Humidity | 5 to 90% RH, non-condensing |
| Dimensions | |
| Dimensions( W x H x D) | 123 mm x 72 mm x 35 mm |
Single-Ended mode can be used for voltage input only.